HFC-227ea is invaluable when protecting a vessel and its crew.
Recommended for manned areas where system discharge can be effected
prior to evacuation of personnel. Cylinders manufactured to BS5045:
Part 2, class 1A and to
BS5423:1977. All units supplied include strong mounting bracket
to facilitate vertical or horizontal mounting. Pressure gauge fitted
as standard on all units. Plastic coating optional. Pressure monitoring
switch optional.
MECHANICAL UNITS
All units supplied with 2 metre long operating cable, pull handle
and protective bracket. Other sizes available on request.
AUTO/MECHANICAL UNITS
All units supplied with 2 metre long operating cable, pull handle
and protective bracket, and a sprinkler bulb operative at a
temperature of 79° C (175° F) as standard. Other ratings
of sprinkler bulb and various sizes of operating cable available
on request.
ELECTRICAL UNITS
All units supplied with latching plug in lead, 2 metres long. Power
source required to operate each unit is 1 amp for 10
milliseconds. Our Research and Development Department is constantly
seeking to improve our products and therefore we reserve the right
to change specification without prior notice.
|